Work with electrical circuit paths and wire sizing
Understand voltage drop and wire size in a circuit.
Step-by-step guide
Understand voltage drop and wire size in a circuit.
- Open the project E01_01.rvt. Ensure the current view is Lighting > Floor Plans > 1 – Lighting.
- Type “ES” on the keyboard to access the electrical settings for this project. Note the values for maximum voltage drop for wire sizing in branch and feeder circuits.
- Click OK.
- In the View tab of the ribbon, create a new schedule for electrical circuits by selecting Schedule/Quantities from the Schedules menu.
- Name the schedule “Branch Circuits”.
- In the Schedule Properties dialog box, from the Available fields list, add Circuit Number, Length, Voltage, and Voltage Drop to the Scheduled fields list.
- In the Filter tab of the Schedule Properties, next to Filter by, select Voltage, select equals, and then select 120V.
- Click OK to close the window and create the schedule.
To create a calculated parameter within the schedule to display the voltage drop as a percentage:
- Click Edit in the Fields parameter of the schedule.
- Click Add Calculated Parameter.
- Name the calculated parameter “% Voltage Drop”.
- Set the Discipline to Common.
- Set the Type to Number.
- Enter the Formula: Voltage Drop/Voltage*100
- Click OK to close the dialog box.
- Change the view to 1 – Lighting.
- Use the TAB key and the mouse button to highlight and select the hallway circuit.
- Review the wire size in the circuit Properties.
- Tile the open views to display the floor plan and schedule.
- Use the method in step 17 to highlight and select the hallway circuit.
- In the Modify | Electrical Circuits tab of the ribbon, click Edit Circuit.
- Select the lighting fixtures in the bottom left corner of the floor plan to add them to the hallway circuit.
- Read and close the warning message.
- Review the calculated values in the schedule and note the increase in % Voltage drop for circuit 3.
- Highlight and select the modified hallway circuit in the view 1 – Lighting, and then in Properties, note the unchanged wire size.
Now, edit the circuit path to see the effect on circuit length and wire size:
- With the hallway circuit still selected, click Edit Path in the ribbon.
- In the Path Mode drop-down, select All Devices, and note the change to circuit length.
- Review the voltage drop value in the schedule, and the wire size in the circuit properties AWG12.
- Edit the path offset to 10' 0", and note that there is no change in the values for voltage drop in the schedule and wire size in the circuit properties.
- Click Finish Editing Path.
- Select the hallway circuit using the method in step 17.
- Click Edit Circuit.
- Add a lighting fixture from any other circuit.
- Ignore and close the warning message.
- Review the circuit properties, noticing the increased wire size due to the voltage drop from this branch circuit having exceeded 2%.
- In the schedule, review the voltage drop for circuit 3, which is now reduced due to the increased wire size.
- Save the project.